Event Power for Crew
B&W Productions · Crew Training · Module 5

Event Power for Crew

Volts, amps and watts. Single-phase and three-phase. Commando plugs, distros and generators, and how to split a 63 A supply down to the socket a speaker plugs into without tripping anything or hurting anyone. South African supply: 230 V single-phase, 400 V three-phase, 50 Hz. Crew plug in; electricians wire in.

B&W Productions · Proper Planning, Prevents Poor Performance Download the PDF booklet
Watch the two-minute narrated summary first, then work through the lessons and the quiz.

01Volts, amps and watts

Three numbers describe every supply and every piece of kit. If you can turn one into the others you can plan the power for any event with a calculator. Think of electricity as water in a pipe.

VOLTS (V)Pressure in the pipe.How hard it pushes.SA: 230 V / 400 V AMPS (A)Flow through the pipe.How much is moving.What breakers measure WATTS (W)Work done. Pressure × flow.What the kit label says.W = V × A AMPS = WATTS ÷ VOLTS  ·  1 000 W ÷ 230 V = 4.3 A
The voltage in South Africa is fixed by the supply. The watts are fixed by the kit. The only thing you ever calculate is amps, because amps are what trip breakers and melt cables.
The only sum you need
Amps = Watts ÷ 230. Add up the watts on a cable, divide by 230, and compare with the breaker. Stay under 80% of the breaker (12.8 A on a 16 A, 25.6 A on a 32 A, 50 A on a 63 A).

02Single-phase and three-phase

Mains power is alternating current (AC): it swings positive and negative 50 times a second (50 Hz). A single-phase supply is one of those swings on one live wire. A three-phase supply is three swings on three live wires, each a third of a cycle behind the last. Big kit and big sites use three-phase because it carries three times the power on cables that are not three times the size.

L1L2L3 Each phase peaks a third of a cycle (120°) after the last. Together they never all drop to zero at once. THE FIVE WIRES (5-PIN RED PLUG) L1 · brown · live 1 L2 · black · live 2 L3 · grey · live 3 N · blue · neutral E · green/yellow · earth Any live to neutral: 230 V (single-phase). Any live to another live: 400 V. Single-phase kit only ever sees one live + N + E.
A three-phase supply is three single-phase supplies sharing one neutral. Your sound, lights and bar fridges are all single-phase kit. The distro's job is to hand each of them one phase and keep the three phases evenly loaded.

What this means on site

03Plugs and sockets you will meet

South African event power uses two families: the ordinary 3-pin round plug for the last metre, and the industrial CEE "Commando" plugs for everything upstream. Colour tells you the voltage. Size tells you the current. Pin count tells you single or three-phase. You can only plug a connector into its own matching socket, which is the point: the system protects you from the common mistakes.

ConnectorColourPinsRatingMax power at 80%Where you see it
SA 3-pin round (SANS 164-1) and the newer ZA plug (164-2)white/black316 A2.9 kWThe last extension lead to a speaker, light bar, laptop, urn
16 A Commandoblue316 A2.9 kWDistro outlets, lighting bars, powered speakers with a Commando inlet
32 A Commando single-phaseblue332 A5.9 kWFeeding a single-phase distro, a catering line, a big LED wall processor
32 A Commando three-phasered532 A per phase17.7 kWFeeding a 32 A distro from the 63 A distro
63 A Commando three-phasered563 A per phase34.8 kWGenerator outlet, venue main outlet, into the 63 A distro
125 A Commando three-phasered5125 A per phase69 kWBig stages, LED walls, festival mains. Electrician territory.
16 A · BLUE · 3 PIN230 V single-phase 32 A · RED · 5 PIN400 V three-phase 63 A · RED · 5 PIN · BIGGER
Blue means 230 V. Red means 400 V. A 32 A plug does not fit a 63 A socket, so "it fits" means "it is allowed". Never force, adapt or file a plug.
Adaptors
A 16 A Commando to 3-pin adaptor is fine. A "3-pin to 32 A" adaptor is a death trap: it lets a 3-pin lead carry 32 A, which it cannot. If an adaptor goes from a small plug to a bigger socket, it is wrong.

In the B&W kit: 63 A and 32 A five-core trailing leads, 16 A blue Commando extensions, and standard 3-pin extension leads for the last metre.

04The distro chain

A distro (distribution box) takes one big supply in and gives you several smaller, protected supplies out. Every outlet has its own breaker, so one overloaded speaker trips one outlet, not the whole event. On site, the chain always runs big to small.

GENERATORor venue main outlet63 A three-phase (red 5-pin) 63 A lead 63 A DISTROmain breaker + earth leakage4 × 32 A outputseach with its own breaker spare 32 A 32 A DISTRO · STAGE 32 A DISTRO · LIGHTING 32 A DISTRO · BAR link out NEXT DISTRO FROM A 32 A DISTRO TO THE KIT 32 A DISTRO16 A outlets spread over L1 · L2 · L3 L1 · 16 AFOH speakers subsL2 · 16 A mixer + DJL3 · 16 A 3-pin extension → speaker Rule: big plug upstream, small plug downstream. Never the other way round. Rule: lighting on its own 32 A distro, sound on its own. Dimmers and LED drivers put noise on the line; keep it off the audio.
Generator → 63 A distro → 32 A distros → 16 A outlets → kit. Each step down has a breaker. The 32 A distros have a link-out so you can daisy-chain to the next one across the site, but every box you add on a chain shares the same 32 A.

In the B&W kit: 63 A three-phase distros with four 32 A outputs, and 32 A distros with an in and a link-out that chain to the next distro.

Setting up the chain

  1. Every breaker on every distro off. Earth leakage units reset.
  2. Run the 63 A lead from the generator (or venue outlet) to the 63 A distro. Lay it where nobody walks or drives; ramp it where they must.
  3. Run 32 A leads from the 63 A distro to each 32 A distro. One per area: stage, lighting, bar, catering. Keep the leads short; long runs lose voltage.
  4. Run 16 A Commando or 3-pin extensions from the 32 A distros to the kit. One lead per speaker stack where you can. No daisy-chained extension leads on sound.
  5. Walk the whole chain once with nothing on. Check every plug is fully home and every lead is off the ground where it crosses water.
  6. Power up from the source outwards: generator → 63 A main → 63 A outputs → each 32 A distro main → its outlets → kit, one area at a time. Listen for the earth leakage. If it trips, the fault is on whatever you just switched on.
The link-out is not free power
A 32 A distro's link-out passes the same 32 A on to the next box. Three distros on one chain still share 32 A total. Chain for distance, not for capacity.

05Load and phase balance

Two sums before every event: does each cable stay under 80% of its breaker, and are the three phases carrying roughly the same load? An unbalanced three-phase supply trips one phase early while the other two sit idle, and it makes a generator run badly.

Try it: load the distro

ItemWatts eachQty
Powered top (12")500
Powered sub800
Mixer + DJ + laptops300
LED PAR can150
Moving head350
Slush machine800
Tea urn / kettle2000
Bar fridge300
0 kW
total load
0 A
total amps at 230 V
0 A
per phase if balanced
0%
of breaker

How to balance

06Breakers, earth leakage and leads

Everything between the source and the kit exists to break the circuit before a person or a cable gets hurt. Learn what each device does so you know what it means when one trips.

MCB (breaker)

Trips on too much current: an overload or a dead short. If it trips, you have too much plugged in or a damaged lead. Unplug, find it, reset once. If it trips again, stop and call it in.

Earth leakage (RCD/ELU)

Trips when current leaks to earth, which is usually through a person or water. 30 mA in milliseconds. Nuisance trips come from wet leads, cracked plugs, and a long chain of LED fixtures each leaking a little. It is never bypassed. Ever.

Main breaker

The big switch on the distro. Off before you plug in, on last. It is also your emergency stop for that whole area.

Cable rating

A lead is rated for the plug on its end, if it is the right cable. 2.5 mm² for 16 A, 6 mm² for 32 A, 16 mm² for 63 A. A thin "household" extension on a 16 A Commando is a fire.

Extension leads: the three rules

  1. Unroll cable drums fully. A coiled drum carrying load is a heater. The rating on the drum halves when it is wound.
  2. One lead, one job. No lead into a lead into a multiplug. Every join is a weak point, a trip hazard and a place water gets in.
  3. Short runs for big loads. Voltage drops along a cable. 50 m of 2.5 mm² lead feeding a 3 kW load loses enough voltage that amplifiers clip early and heaters run cold. Move the distro closer instead of running the lead longer.
DISTRO 230 V SPEAKERgets ~218 V 50 m of 2.5 mm² at 13 A: about 12 V lost as heat in the cable Keep lead runs under 25 m for anything over 2 kW. Bring the distro to the load.
Volt drop is invisible until an amp starts clipping or a breaker trips "for no reason". The fix is a shorter lead or a thicker one, never a bigger breaker.

07Generators

When there is no mains, or the venue's supply is too small, the generator is your power station. Treat it as the most important piece of kit on site: if it stops, everything stops.

In the B&W kit: a 32 kVA three-phase diesel generator with a 63 A five-pin outlet.

kVA, kW and headroom

GeneratorUsable (kW)Plan for (70%)Rough diesel use at that loadWhat it runs
20 kVA1611 kW~3 to 4 L/hSmall PA, 16 LED pars, a bar, one urn
32 kVA2518 kW~5 to 6 L/hFull small-event rig: PA with subs, lighting, catering, slush, fridges
60 kVA4834 kW~9 to 11 L/hStage with moving heads, LED wall, catering kitchen

Fuel figures are planning estimates. Check the set's own plate and fill before every event; an 8-hour corporate day on a 32 kVA set is roughly 40 to 50 litres.

Placing the generator

GUESTS · STAGE · MARQUEE GENERATOR 10 m + exhaustdownwind wind → drip tray · fence · extinguisher 63 A lead runs along the edge, ramped at the walkway, never under the dance floor
Far enough that guests do not hear it or breathe it, close enough that the 63 A lead stays short. Level ground, a drip tray, a fire extinguisher, and nobody parks against it.

Start-up and shutdown

  1. Fuel, oil and coolant checked. Earth spike connected (the hire company or electrician does this; you confirm it is there).
  2. Main output breaker off. Start the engine. Let it run 3 to 5 minutes with no load.
  3. Main breaker on. Then the 63 A distro, then each 32 A distro, then kit, one area at a time.
  4. Shutdown in reverse: kit off, distros off, main breaker off, let the engine run 2 to 3 minutes unloaded, then stop it. Never stop a diesel under load.
  5. Refuel only with the engine off and cool. Log the hours.

0863 A vs 32 A vs 16 A: what goes where

The number on the plug is the most current that cable and socket may carry. Here is the same rule from the other direction: how much kit each supply can feed, and which supply each job needs.

SupplyMax at 80%FeedsTypical job
16 A single-phase2.9 kWOne speaker stack, or 10 LED pars, or one urnThe last lead to a piece of kit
32 A single-phase5.9 kWA small PA with subs, or a catering lineOne area from a single-phase source
32 A three-phase17.7 kWA whole small event: PA, lights, bar, cateringOne 32 A distro per area of the site
63 A three-phase34.8 kWFour 32 A distros, or a stage with moving heads and an LED wallThe main feed from generator or venue
16 A 1φ2.9 kW 32 A 1φ5.9 kW 32 A 3φ17.7 kW 63 A 3φ34.8 kW usable power at 80% of rating · blue = single-phase 230 V · red = three-phase 400 V
Three-phase triples what a plug of the same amp rating can feed. That is why the site feed is red and the kit feed is blue.
Venue power check, before you quote
Ask the venue: "What is the biggest outlet near the stage and is it three-phase?" A 16 A wall socket runs a speech system. A 32 A single-phase runs a small party. Anything with subs, moving heads and catering wants a 32 A three-phase or a generator.

09Safety, and where crew stop

Event power kills people every year, almost always through water, damaged leads or someone opening something they should not. The rules are short because they have to be followed every time.

The line
Crew plug in. Crew never wire in. Tails, distribution boards, generator earth spikes, anything with a screwdriver: a registered electrician does it and signs for it. If a plug, lead or distro is damaged, it is tagged "OUT OF SERVICE" and goes back to the warehouse.

Every event

Fast fault-finding

SymptomCheck firstThen
Earth leakage trips at switch-onWhich outlet did you just switch on? Unplug it, reset, try the restWet plug or lead on that outlet; swap the lead, then the kit
MCB trips when the music gets loudToo many amps on one 16 A outletMove the subs to their own outlet on another phase
Trips at 15:00 when catering startsUrns and heaters added to a loaded phaseCatering on its own 32 A distro
Speakers clip early, lights dim when the urn boilsVolt drop on a long lead or an overloaded generatorShorter lead, distro closer, check generator load %
Hum in the soundSound and lighting sharing a phase or a distroSeparate distros; ground-lift the DI
Generator hunting or stallingLoad too high, or switched on all at onceShed load, restart in stages, check fuel
Plug warm to touchLoose pin, not fully home, or a lead rated too smallSwitch off, swap the lead, tag the warm one

Before you leave the warehouse

10Check what you learnt

Ten questions. Pick an answer for each, then press Mark my answers. You need 8 out of 10 to pass this module. You can retry as often as you like.

Answer key