B&W Productions · Crew Training · Module 8

Event Power in Depth

Module 5 gave you the basics. This module goes deeper: build a load sheet, stop multiplugs and couplers overloading, keep joints dry, size and run a 20, 30 or 50 kVA generator, balance three phases, understand earth leakage, and know exactly where crew stop and the electrician starts. Two live tools let you try the sums.

B&W Productions · Proper Planning, Prevents Poor Performance Download the PDF booklet
Watch the two-minute narrated summary first, then work through the lessons and the quiz.

01The load sheet: what your kit actually draws

Module 5 taught you amps = watts ÷ 230. This lesson is the next step: write down every item that will be plugged in, find its real draw, and work out the supply before you leave the warehouse. That list is the load sheet. A load sheet that is wrong by a few kilowatts is how a show goes dark at 20:00.

Running watts and inrush

Every item has two numbers. Running watts is what it draws once it has settled. Inrush is the surge at the moment of switch-on. Amplifiers, powered speakers and the motors in moving heads can pull several times their running current for a fraction of a second. A breaker sees that surge. Switch ten items on together and the surges stack on top of each other.

ALL AT ONCEIN GROUPS TRIP LEVELTRIP LEVEL SWITCH-ON running level 123 Breaker trips Every spike stays under
Same kit, same running level. Switched on all at once, the surges add up and cross the trip level. Switched on in groups with a few seconds between, each surge fades before the next starts.
Power up in groups
Biggest and most surge-prone first: amp racks and subs, then tops, then moving heads, then LED PARs, then catering. A few seconds between groups. Never throw every breaker at once.

Typical draws

These are planning ranges, not specs. Your own kit has a label or plate with the real number. Check the label and use that. When the label gives a maximum, remember most kit runs well below it, so the label is the safe side of the sum.

CategoryTypical running drawSwitch-on surgeNote
Powered top200 to 600 WNoticeableDraw climbs with volume. Label shows the maximum.
Powered sub400 to 1 000 WNoticeableThe biggest sound load per box.
Amp rack500 to 2 000 WHighDepends how hard it is driven. Use the plate.
LED PAR40 to 150 WLowMany small loads add up fast.
Moving head150 to 400 W (LED); 400 W up for lamp typesHighMotors reset all at once at power-up.
Haze or smoke machine500 to 1 500 WNone (heater)Heater load while warming up.
Tea urn2 000 to 3 000 WNone (heater)Steady and big. One urn is a whole 16 A circuit.
Laptop, DJ gear100 to 400 WLowSmall, but it must never lose power.

B&W habit: the PA (amp racks, tops and subs) goes on its own phase, lighting and effects on another, and catering and heaters on the third.

Try it: build a load sheet

Pick a quantity for each item and the phase it plugs into. The tool adds it up and tells you the smallest supply that fits at 80%. Values are mid-range planning figures: replace them with the label on your own kit.

ItemPlanning W eachQtyPhase
400
600
1500
80
250
800
2000
200
0 W
Total load
0 A
Total amps at 230 V
0 / 0 / 0
Amps on L1 / L2 / L3
0 A
Worst phase
-
Smallest supply at 80%
Add some kit.

02Sockets, multiplugs and couplers: not overloading

Overloaded multiplug with a second multiplug daisy-chained into it and a scorch mark
What not to do: a multiplug plugged into a multiplug, every socket full. The scorch mark is the warning you get before the fire.

Most overloads are not at the generator. They are at the last few metres, where one cheap multiplug feeds far more than it can carry. The rule is simple: every joint in the chain is only as strong as its weakest part.

DISTRO OUTLET32 A breaker behind it32 A available 16 APLUG MULTIPLUGrated by its plug: 16 A AMP RACK · 7 A AMP RACK · 7 A AMP RACK · 7 A 21 A of kit through a 16 A plug: it heats, the 32 A breaker never notices
A breaker protects the cable behind it, not whatever is plugged in downstream. The plug on the multiplug is the limit, so the multiplug is a 16 A multiplug no matter how big the outlet is.

The rules

WOUND: heat is trapped, low rating UNWOUND: heat escapes, full rating
Both reels hold the same cable. Only the unwound one can shed the heat it makes.
No exceptions
Never fit a bigger breaker or fuse to stop trips. The trip is telling you the load is too big for that circuit. Move load to another outlet or another phase.

03The chain on site

Power always steps down: big and protected at the source, smaller and protected again at every step. Know what each link is rated for and you know what it can carry. This is the chain you will build on most jobs.

GENERATOR63 A outletred 5-pin 63 A DISTROfour 32 Aoutputs 32 A DISTRO32 A in, 3 phases15 × 16 A, 5 per phase MULTIPLUG16 A plugmax 12.8 A KITspeakers, lights,laptops 63 A32 A lead (red, 5-pin)16 A16 A 63 A 32 A 32 A 16 A 16 A work to 50 Awork to 25.6 Awork to 25.6 Awork to 12.8 A12.8 A per plug Rating at each step. "Work to" is 80% of the rating.
Each step down has its own breaker. A link-out passes the same current on to the next box, so a second distro chained off the first still shares the first one's 32 A.

In the B&W kit: the generator's 63 A red five-pin outlet into a 63 A distro (one 63 A inlet, four 32 A three-phase outputs, an ammeter per phase on the front), red 32 A five-pin leads to the 32 A distros (a 32 A three-phase inlet, 15 plug-top outlets, five per phase, each with its own trip switch), multiplugs off those outlets, and Janus couplers on the last metre.

Adaptors: what is allowed

AllowedNever
Bigger supply to a smaller one, when the smaller one has its own protection. A 32 A distro outlet down to a 16 A lead is the normal case.A small plug into a bigger socket. A 16 A lead pushed into a 32 A feed with an adaptor carries 32 A in a 16 A cable.
A purpose-made adaptor that is the same make as the connectors, undamaged and tagged.Home-made adaptors, cut-off plugs, "temporary" wiring, a plug with the pins bent to fit.
The lead whose plug matches the socket. Colour and pin count match, so it only fits where it belongs.Forcing a plug that does not fit. If it does not fit, it is not meant to be used there.
Read the chain from the kit back
Add up the amps on each multiplug. Add the multiplugs on each 32 A distro. Add the 32 A distros on the 63 A distro. At every step the total must be under the rating, and under 80% of it.

04Water and weather

Water and power kill. Rain, a leaking tent, a watered lawn or a cooler box of melting ice all find the joints in your chain. Plan for water before it arrives. The rating on a piece of kit tells you what it was built to survive.

IP ratings

IP 6 5 FIRST DIGIT: SOLIDS AND DUST 0 = no protection 4 = keeps out objects over 1 mm 5 = dust protected 6 = dust-tight SECOND DIGIT: WATER 4 = splashes from any direction 5 = water jets 6 = powerful jets 7 = temporary immersion
Higher number, better protection. A rating only holds for a closed, fully connected item. An open socket or a plug half in is IP-nothing.
RatingMeansUse it for
IP20No water protectionIndoors, dry, under a roof only
IP44Splash-proofCovered outdoor use, a light drizzle on a covered stage
IP65Dust-tight, water jetsOutdoor lights that get rained on
IP66Dust-tight, powerful jetsHeavy rain and hosing down
IP67Dust-tight, temporary immersionKit that may sit in a puddle for a short while

Joints are the weak point

A plug and socket joint is the least waterproof part of your chain, whatever the equipment says. Janus rubber couplers are not waterproof. They stop fingers touching live pins. They do not stop water running in.

PUDDLE PATH: keep joints out CRATE OR BRICKS COUPLER COVER BOX, LID DOWN DRIP LOOPDRIP LOOP Water runs down the cableto the low point and drips off,not into the joint.
Cover box on a crate, cables dipping below the box and rising into it, nothing downhill from a puddle.

At B&W the Janus couplers on the last metre are rubber like any other: they get a cover box, a crate and a drip loop, and they are never left in a wet path.

If a joint has been under water
Switch off at the source. Do not touch it while it is live. Tag it. A qualified electrician checks it before it is used again, even if it looks dry.

05Generator sizes: 20, 30 and 50 kVA

A generator sets the ceiling for the whole event. Pick one too small and the show trips. Pick one far too big and the engine suffers. The numbers below get you close; the plate and the hire company give the exact figures.

SetkW (kVA × 0.8)On the Highveld (about −10%)Plan for 70% of thatUnder-loaded below 30%
20 kVA16 kW14.4 kW10.1 kW4.3 kW
30 kVA24 kW21.6 kW15.1 kW6.5 kW
50 kVA40 kW36 kW25.2 kW10.8 kW

B&W has 20, 30 and 50 kVA generators, each as a single-phase or a three-phase unit. Read the plate on the set in front of you before you plan the load.

UNDER-LOADEDGOOD BANDTIGHT 0%30%70%100% wet stacking riskplan to be hereno room for a surge beyond 100% = too small, it trips
Percent of the generator's available kW after derating. Aim for the green band. If the load is below it, hire the next size down.

Try it: size a generator

-
Rated kW (kVA × 0.8)
-
Usable kW after derating
-
Plan-for ceiling (70%)
-
Loaded
-
Amps per line

06Single-phase vs three-phase generators

The same kVA can be delivered two ways. A single-phase set gives you one supply. A three-phase set gives you three. Which you have changes how you plan the load.

Single-phase set

One 230 V supply. All the load is on one line, so the total amps are the line amps. Simple, and fine when the total load is small. The distro just splits that one line into outlets.

Three-phase set

Three 230 V lines (L1, L2, L3) and 400 V between any two of them. Each line carries a third of the set. You must spread the load across the three lines.

Why balance matters

On a three-phase set each line can only give about a third of the rating. A 30 kVA set gives roughly 10 kVA per line. Overload one line and it sags or trips while the other two have room to spare. The set looks half empty and still fails. A badly unbalanced load also makes the voltage on the loaded line drop, and that is when amplifiers clip early and lights flicker.

BALANCEDUNBALANCED LIMIT PER LINELIMIT PER LINE L1 · 14 AL2 · 14 AL3 · 14 A L1 · 30 AL2 · 8 AL3 · 4 A Same 42 A total, no line near the limitSame 42 A total, one line over
Both cases carry 42 A in total. Only the balanced one works. The imbalance figure is the difference between the heaviest and lightest line, as a share of the heaviest.

Reading the three ammeters

A three-phase distro with meters on the front shows one reading per phase: L1, L2 and L3. Each meter shows the amps that phase is carrying right now. That is your load sheet, live.

63 A DISTRO · FRONT PANEL 18 AL1 22 AL2 41 AL3 · heavy Total 81 A. Every phase is under 63 A, but L3 carries half the load. Move something off L3 onto L1.
Read the meters with the full show running: the PA at show level, all the lights on, the urns boiling. A quiet soundcheck reading is not the real number.

On the B&W 63 A distro the three meters are on the front. Read them after each area comes on. The B&W 32 A distros have no meters, but their 15 outlets are grouped five per phase with a trip switch each, so you balance by choosing which group an item plugs into. Remember the sum: five 16 A outlets on one phase still share that phase's 32 A. Five urns on one phase will trip it.

A sensible split

Keeping sound on its own line also keeps lighting dimmers and heater switching away from the audio. Label each outlet with its line (for example "L2 · lights").

When single-phase is enough
A small PA, a few lights and a laptop: total under about 10 A and nothing heavy like an urn on it. If you need to ask whether single-phase is enough, run the load sheet from Lesson 1. If the total is over 25.6 A, you want three-phase.

07Running a generator on site

Electrician checking an earth spike beside a trailer generator
The earth spike and its lead are the electrician's job. Crew never pull it out, move it or park on it.

A generator is a running engine in a public space. It makes noise, heat and a poisonous gas. Most trouble comes from where it stands and how it is started and stopped.

STAGE63 A distro here GUESTS AND TENTkeep exhaust away from here CORDON: nobody inside GENERATOR exhaust EXT. earth spike 63 A lead, off the ground, ramped where crossed 10 m or more WIND: from guests toward generator LEVEL GROUND, drip tray under the set
Downwind, away from guests and tents, on level ground, in the open. Not under an awning, not in a container, not beside an air intake.
Carbon monoxide
Exhaust has carbon monoxide: you cannot smell it and it kills. Never run a generator in a closed space, a tent, a container or a garage, and never where the exhaust can blow into one.

Placement

On a B&W job the electrician decides where the generator stands and earths it. Crew cordon it, fuel it and watch it.

Fuel at a glance

A diesel set at a decent load uses roughly 0.3 litres per kWh of load. The set's own data plate or the hire company gives the real figure. Example: a 15 kW load for 10 hours is about 15 × 10 × 0.3 = 45 litres. Add a 25% reserve and fill to at least that before the event starts. Refuel only when the set is stopped and cool. Fuel on a hot exhaust is a fire. Never let it run dry: it also stalls the engine and can need bleeding.

Start-up and shutdown

  1. Check fuel, oil and coolant. Confirm the earth spike is in place.
  2. Main breaker off. Start the engine with no load. Let it warm up for a few minutes.
  3. Switch on in groups (Lesson 1): main breaker, then distros, then kit in the order you planned.
  4. Check the percentage load stays in the good band (Lesson 5).
  5. Shutdown: kit off, distros off, main breaker off. Let the engine run unloaded for a few minutes to cool, then stop it. Never stop a diesel under load.

08Earth leakage and protection

Two different devices protect you, and they trip for different reasons. Knowing which one tripped tells you where to look.

SUPPLY EARTH LEAKAGEcompares out and back KITdamaged or wet liveneutral leak to earth (through you) Out is bigger than back: TRIP
The earth leakage unit compares the current going out with the current coming back. A difference of 30 mA or more means current is going somewhere it should not, and it cuts the circuit in a fraction of a second.
Breaker (MCB)Earth leakage (RCD)
Trips onToo much current: overload or short circuitCurrent leaking to earth, often through a person or water
ProtectsThe cable and kit from overheatingPeople from shock
Typical trip levelIts rating: 16 A, 32 A, 63 A30 mA on the 16 A outlets
Usual causeToo much on one outlet, a damaged leadWet plug, damaged lead, faulty kit

On B&W distros every outlet group has its own trip switch. Know which switch feeds which outlets before the show, and test the earth leakage button where the distro has one. A distro with no earth leakage on its 16 A outlets goes to the crew chief before anything is plugged in.

Test, then trust

A trip is information
Reset once. If it trips again, find the cause. If you cannot find it, switch off and call the engineer or the electrician.

09Who does what, legally

Event power is covered by law in South Africa. The rule on site is short: crew plug in, electricians wire in.

Crew

Place distros. Lay leads. Plug into the right socket, switch on in groups, watch for heat, trips and damage, and report faults. Fill and watch the generator.

Registered electrician

Anything wired: tails, a distribution board, a generator hook-up that is not a plug, the earth spike, repairs inside a plug or distro. They also sign for the installation.

Why the line matters
If you wire in and something goes wrong, you may be personally liable, and insurance may not cover it. If you plug in and report a fault, you have done your job.

10Pre-show power checklist and fault table

Run this list for every event. Tick each item as you check it. It takes ten minutes and finds most problems before the guests arrive.

  1. Load sheet done
    Every item listed, watts and amps worked out, supply chosen at 80%, phases within 30% of each other.
  2. Generator sized and placed
    Right size for the load in the good band (30 to 70%), level ground, 10 m from guests, exhaust downwind, cordon up, extinguisher beside it.
  3. Fuel
    Enough for the whole event plus a reserve. Refuel plan agreed: stopped and cool only.
  4. Earth spike confirmed
    Installed and checked by the electrician. Not touched by crew.
  5. All leads inspected
    No cuts, crushed sections, bent pins or loose glands. Damaged ones tagged out.
  6. Multiplugs checked
    Each under 12.8 A, none chained, reels fully unwound.
  7. Joints protected
    Cover boxes on, lifted off the ground, drip loops, away from puddle paths, CEE caps closed on unused sockets.
  8. Earth leakage tested
    TEST button on every unit trips and resets.
  9. Outlets labelled by phase
    L1 sound, L2 lighting and effects, L3 catering and heaters.
  10. Power up in groups
    Generator no load, main, distros, then kit: amp racks and subs, tops, moving heads, PARs, catering. Percentage load checked at the end.
0 of 9 done.

If it is wrong

SymptomMost likelyCheck
Breaker trips at switch-on, holds when you try againSurges stacked: too much switched on at oncePower up in groups; biggest first
Breaker trips after a while under loadOverload on that outletAdd up the amps on that outlet; move kit to another outlet or phase
Earth leakage trips as soon as one outlet is switched onWet or damaged lead or kit on that outletUnplug everything on it, reset, plug back in one by one
Earth leakage trips when rain startsWater in a jointCover boxes, lifted joints, drip loops; dry and electrician-check any joint that was wet
Plug or multiplug warmOverloaded or looseSwitch off, unplug, tag, shed load
One phase dead, others finePhase breaker tripped or unbalanced overloadCheck that phase's breaker and load; rebalance
Lights dim and amps clip as the urn boilsVoltage sag on a loaded phaseMove the urn to its own phase; check generator percentage
Black smoke, soot, power seems lowWet stacking: generator under-loadedAdd load or swap to a smaller set
Generator hunts, surges or stallsOverloaded, switched on too fast, or low on fuelShed load, restart in groups, check fuel
The whole module in one line
Sum the load, spread the phases, stay under 80%, keep joints dry, switch on in groups, and let the electrician do the wiring.

11Check what you learnt

Ten questions. Pick an answer for each, then press Mark my answers. You need 8 out of 10 to pass this module. You can retry as often as you like.

Answer key

    Photos: product images courtesy of the manufacturers (RCF, Neutrik) and their distributors; scene photographs are AI-generated illustrations and do not show B&W Productions equipment or events.